전기 절연 매트의 치수 및 허용 오차: 대량 구매자가 두께, 너비 및 롤 길이에 대해 확인해야 할 사항

Bulk buyers often send us a specification such as:

Electrical insulating mat, 5 mm × 1 m × 10 m.

These dimensions are useful, but they do not form a complete purchasing specification.

Before production, buyers should confirm whether the dimensions are nominal or minimum values, which tolerances apply, how thickness will be measured, whether warning borders are included in the stated width, and whether each roll must provide a guaranteed continuous usable length.

These details affect delivered area, roll quantity, layout planning, inspection, invoicing, and project acceptance.

현지 규정 및 현장 안전 절차를 준수하십시오.

Quick Answer: Nominal Size Is Not the Complete Specification

A nominal size such as 5 mm × 1 m × 10 m normally describes the target product dimensions. It does not necessarily mean that every thickness point measures exactly 5.00 mm or that every roll must contain at least 10.00 m of usable material.

Before approving a bulk order, confirm:

  • 적용 표준
  • Electrical class
  • 공칭 두께
  • Declared thickness range
  • Thickness measurement reference
  • Nominal roll width
  • Minimum usable width
  • Nominal or guaranteed roll length
  • Whether negative tolerance is accepted
  • Whether joins are permitted
  • Sampling and inspection requirements
  • Roll identification and traceability

IEC 61111:2009 applies to elastomer electrical insulating matting used as protective floor covering for workers on electrical installations. Its dimensional rules treat length and width differently from thickness.

Start with the Standard and Electrical Class

Dimensions should not be selected before the required standard and electrical class are confirmed.

Thickness alone does not determine:

  • Electrical class
  • 최대 작동 전압
  • Proof-test performance
  • 유전 성능
  • Suitability for a particular installation

A thicker general-purpose rubber sheet is not automatically equivalent to a classified electrical insulating mat.

For IEC-based projects, the buyer should first define the required IEC 61111 class. Thickness, surface pattern, width, roll length, color, and packing can then be specified within the approved product design.

Buyers who still need to confirm the electrical class can review our guide to IEC 61111 전기 절연 매트 요구사항 그리고 우리의 범위 IEC 61111 전기 절연 매트.

공칭 두께와 실제 두께

A bulk purchase specification should distinguish between the nominal thickness and measured thickness.

기간구매자에게 의미하는 바
공칭 두께The target thickness stated in the quotation, datasheet, and product model
Actual readingThe thickness measured at one defined point
Declared thickness rangeThe manufacturing range proposed by the supplier
Minimum recorded thicknessThe lowest result found under the agreed inspection method
Maximum recorded thicknessThe highest result found under the agreed inspection method
Standard maximum thicknessThe maximum permitted for an IEC class
평균 두께The calculated average of several readings, where required

A nominal 5 mm mat will not necessarily measure exactly 5.00 mm at every point.

Rubber manufacturing, surface profile, material flow, trimming, and measurement position can create small variations. The important issue is whether the actual readings meet:

  1. 적용 가능한 표준
  2. The supplier’s declared manufacturing range
  3. The buyer’s contractual acceptance requirement

The buyer should not assume a thickness tolerance that has not been stated.

IEC 61111 Does Not Give One General ±2% Thickness Tolerance

A common purchasing error is to apply the IEC length-and-width tolerance directly to thickness.

IEC 61111:2009 states that the declared length and width should remain within ±2% of the stated dimensions. Thickness follows a different control method.

The standard specifies maximum thickness by electrical class:

IEC 클래스최대 두께
클래스 06.0 mm
클래스 16.0 mm
클래스 28.0 mm
클래스 311.0 mm
클래스 414.0 mm

The minimum thickness is determined by the product’s ability to pass the required tests. Therefore, IEC 61111 should not be described as providing a universal ±2% thickness tolerance.

A supplier may declare its own manufacturing tolerance, and a buyer may establish a contractual tolerance. However, these should be identified as supplier or contract requirements rather than incorrectly presented as the general IEC thickness rule.

What Buyers Should Request for Thickness Control

생산 전에 다음 사항을 확인하십시오.

  • 공칭 두께
  • Supplier’s proposed thickness range
  • Whether a minimum individual reading applies
  • Whether an average reading applies
  • Maximum individual reading
  • 측정점수
  • 측정 위치
  • Edge-exclusion rule
  • Surface-profile reference
  • 검사 장비
  • 샘플링 수량
  • 보고 형식

A vague specification such as “5 mm thickness” can lead to disagreement.

A clearer requirement might state:

Nominal thickness: 5 mm. The supplier shall declare the proposed manufacturing range before production. Pre-shipment records shall show the minimum, maximum, and average readings for each sampled roll.

The buyer should confirm that this requirement is technically compatible with the selected IEC class and product design.

Surface Pattern Changes the Thickness Measurement

Surface pattern affects where thickness is measured.

Common insulating mat surfaces include:

  • 부드럽게
  • 가는 리브
  • 골판지
  • 다이아몬드
  • 박차를 가한
  • 질감

For corrugated or diamond-pattern IEC 61111 matting, thickness measurements are taken over the raised corrugations or diamonds. IEC 61111 also limits corrugation depth and diamond height.

This matters because different measurement positions can produce different readings.

For example, measuring the valley of a corrugated mat and comparing it with a total profile thickness can create an artificial discrepancy.

The RFQ should clarify whether the reported dimension means:

  • Total thickness over the surface profile
  • Base thickness, if separately required
  • 프로필 높이
  • Overall finished thickness
  • Thickness measured according to the applicable standard

The buyer should not require a non-standard measurement method and then use that result to reject a product tested under the standard method.

Width Tolerance: Nominal Width vs Finished Width

IEC 61111:2009 states that the manufacturer-declared length and width should remain within ±2% of the stated dimensions.

For a nominal width of 1,000 mm, a ±2% dimensional range would be:

  • 최소: 980mm
  • 최대: 1,020mm

This example applies only when IEC 61111 and its dimensional rule form the agreed purchasing basis.

A buyer may require a narrower range or a guaranteed minimum width. That additional requirement should be stated in the RFQ and purchase order.

예 :

Nominal roll width: 1,000 mm. Minimum finished width: 1,000 mm. Negative width tolerance is not accepted.

This is a contractual requirement. It is stricter than accepting the full standard tolerance and may affect production feasibility and price.

Gross Width vs Usable Width

The stated roll width may not always equal the usable working width.

Buyers should distinguish between:

  • Gross roll width
  • Finished edge-to-edge width
  • 트리밍된 너비
  • Usable insulating width
  • Main-color working area
  • Warning-border-inclusive width

This is especially important for mats with colored warning edges.

For example, a black mat may have a yellow border along one or both sides. The buyer should ask:

Is the stated 1,000 mm width the full finished roll width, or does it refer only to the black working area?

If the yellow border is included in the overall width, the central black area will be narrower than the declared full width.

견적요청서(RFQ)에는 다음 사항이 명시되어야 합니다.

  • Total finished width
  • Width of each warning border
  • Usable central width
  • Border position
  • Border dimensional tolerance
  • Whether markings are included within the width

Buyers sourcing this design can compare the available format on our warning yellow edge electrical insulating mat 제품 페이지.

Roll Length: Nominal, Minimum, or Guaranteed?

The phrase “10 m roll” can have several commercial meanings:

  • Nominal length of 10 m
  • Target production length of 10 m
  • Length subject to an agreed tolerance
  • Minimum guaranteed length of 10 m
  • 약 10m
  • Invoiced as a 10 m nominal roll

These descriptions are not equivalent.

If a stated 10 m length is accepted with a ±2% dimensional tolerance, the resulting permitted range would be 9.8–10.2 m.

If the project needs at least 10 m of continuous usable material, the RFQ should say:

Minimum usable continuous roll length: 10.0 m. Negative length tolerance is not accepted.

This is particularly important where one roll must cover a long switchgear lineup without an additional seam.

Buyers should confirm whether the supplier can provide the required guaranteed minimum before the order is approved.

Continuous Roll Length, Joints, and End Sections

Roll length should not be reviewed only with a tape measurement.

Buyers should also confirm whether the stated length is:

  • One continuous piece
  • Free from splices
  • Free from bonded joints
  • Measured before or after trimming
  • Inclusive of irregular end sections
  • Inclusive of damaged or unusable material
  • Inclusive of leader material used for production or packing

A bulk RFQ should state whether joins are permitted.

Recommended wording may include:

Each roll shall be supplied as one continuous length. Spliced, bonded, or mechanically joined sections are not accepted unless approved in writing.

The buyer should also define how damaged ends are treated. A roll may technically meet the total length but provide less usable material if one end is crushed, split, contaminated, or irregularly cut.

Nominal Area vs Actual Delivered Area

A nominal roll of 1 m × 10 m is generally described as 10 m².

However, if both width and length are below their nominal values within an accepted tolerance, the actual measured area will also be below the nominal area.

This difference becomes important when:

  • Many rolls are purchased
  • Coverage is calculated closely
  • Material is invoiced by square metre
  • A project has limited cutting allowance
  • Long continuous standing zones are required
  • Replacement stock is not available locally

The purchase order should define how quantity is calculated:

  • By number of rolls
  • By nominal square metres
  • By guaranteed minimum square metres
  • By actual measured square metres
  • By cut pieces of stated minimum dimensions

The commercial basis should match the technical acceptance basis.

A supplier should not invoice by nominal area while the buyer expects guaranteed minimum measured area unless this has been agreed.

Width and Roll Length Affect Layout Planning

The dimensional acceptance specification should connect with the site layout.

For switchgear rooms, the buyer normally starts by measuring:

  • 패널 전면
  • Operator standing-zone depth
  • 문틈
  • Seam positions
  • 롤 방향
  • 절단 여유분

우리의 가이드 배전반실 매트 면적 측정 방법 explains this site-planning stage.

Once the required coverage has been calculated, the buyer should add the manufacturing and cutting allowance.

For example, a project requiring exactly 20 m of continuous coverage should not order only two nominal 10 m rolls if negative tolerance, trimming, or site cutting may reduce the usable length.

The project quantity should account for:

  • Permitted dimensional tolerance
  • 엔드 트리밍
  • On-site cutting
  • 솔기
  • 장애물
  • Damaged-section contingency
  • Future replacement stock

Roll-to-Roll Consistency in Bulk Orders

An approved pre-production sample does not automatically prove that every production roll has the same dimensions.

A bulk inspection plan may include rolls from:

  • The beginning of production
  • The middle of production
  • The end of production
  • Different batches
  • Different production dates
  • 다른 색상
  • 다양한 표면 패턴
  • Different widths or thicknesses

The inspection record should identify each sampled roll.

유용한 정보는 다음과 같습니다.

  • 롤 번호
  • 배치 번호
  • 생산 일
  • 공칭 치수
  • Thickness readings
  • Actual width
  • 실제 길이
  • 표면
  • 색상
  • 검사관
  • 검사일
  • 맺음말

The sampling level should be agreed before production. Buyers should not request an undefined “dimensional report” after the goods have already been packed.

Standard Requirements and Contract Requirements Are Different

Buyers should separate standard compliance from project-specific acceptance.

요구사항 유형예시
표준 요구 사항IEC 61111 length and width tolerance
Standard class limitMaximum thickness for the selected IEC class
Product declaration5 mm nominal thickness
제조업체 역량Declared production range of the selected compound
Buyer contract requirementMinimum usable width of 1,000 mm
프로젝트 요구 사항No roll shorter than 10.0 m
검사 요건Recorded readings from sampled production rolls
포장 요구사항Roll number shown on the label and inspection report
Commercial requirementInvoicing based on guaranteed usable area

A product may comply with IEC 61111 but still fail a stricter project-specific dimensional requirement.

The reverse is also important. Meeting an exact physical dimension does not prove electrical compliance.

The standard, electrical class, dimensions, test evidence, and contract acceptance requirements should all be reviewed together.

구매자가 견적 요청서(RFQ)에 포함해야 할 사항

RFQ 필드Information to Define
StandardIEC 61111 or another project-required standard
Electrical classRequired class based on the system
공칭 두께Target finished thickness
두께 범위Supplier declaration or buyer-required range
측정 방법Surface reference and reporting method
공칭 너비Target finished roll width
Minimum usable widthRequired working width after borders or trimming
경고 경계Border width and whether included in total width
Nominal roll length목표 길이
Minimum usable lengthGuaranteed continuous length, if required
길이 공차Whether negative tolerance is accepted
Roll constructionContinuous roll or whether joins are permitted
표면Smooth, ribbed, corrugated, diamond, or studded
수량 기준Rolls, nominal area, guaranteed area, or measured area
샘플링Number or percentage of rolls to inspect
서류Datasheet, dimensional report, CoC, and roll list
마킹Standard, class, batch, roll ID, and production date
포장Core, wrapping, pallet, edge protection, and roll direction

For standard switchgear and electrical-room formats, buyers can also review our switchboard mat roll options.

공급업체가 반환해야 할 사항

A supplier’s technical offer should state:

  • 적용 표준
  • Electrical class
  • 공칭 두께
  • Declared thickness range
  • Thickness measurement reference
  • 공칭 너비
  • 폭 공차
  • Minimum usable width
  • Warning-border width
  • Nominal roll length
  • 길이 공차
  • Minimum guaranteed length, where offered
  • Continuous or joined roll construction
  • 표면 패턴
  • 롤 무게
  • 포장 치수
  • Sampling proposal
  • Inspection-record format
  • Roll-identification method
  • 기술적 편차

Statements such as “standard tolerance applies” are not enough when several standards or buyer-specific requirements may be involved.

The exact tolerance basis should be named.

입고 검사 체크리스트

항목 확인구매자 질문
Roll identityDoes each roll have a unique roll or batch reference?
Standard and classDo the labels match the purchase order?
공칭 두께Does the product description match the approved specification?
Thickness readingsAre minimum, maximum, and average results available?
Surface referenceWas thickness measured at the agreed position?
완성폭Does the edge-to-edge width meet the agreement?
사용 가능한 폭Are warning borders and trimmed edges treated correctly?
롤 길이Does the usable continuous length meet the order?
관절Are splices or bonded sections present?
종료 조건Are both roll ends usable?
표면Does the finish match the approved sample?
마킹Will required identification remain visible after cutting?
검사 기록Does the record identify the actual sampled rolls?
포장Are the edges and ends protected from transport damage?

Dimensional inspection should be connected to the wider document review.

우리의 가이드 how to read an electrical insulating mat test report explains how dimensions, electrical tests, product marking, batch records, and shipment documents should match.

Common Bulk-Purchase Mistakes

Treating Nominal Thickness as an Exact Reading

Nominal thickness is a target product description. It does not mean every point will have an identical reading.

Applying the ±2% Rule to Thickness

The IEC 61111 ±2% dimensional rule applies to declared length and width. Thickness follows the class limit, product design, testing, and declared manufacturing range.

Measuring a Corrugated Mat in the Valley

A measurement taken from the wrong reference position may not match the standard thickness method.

Ordering “10 m Rolls” Without Defining Minimum Length

If negative tolerance is accepted, a delivered roll may be shorter than 10 m.

Ignoring Usable Width

Warning borders, edge trimming, and damaged edges can reduce the width available for the intended standing zone.

Buying by Square Metre Without Defining the Area Basis

Nominal area, guaranteed area, and actual measured area are not always the same.

Approving One Sample for the Entire Shipment

One sample does not prove dimensional consistency across all production rolls.

Allowing Joints Without Reviewing the Application

A joined roll may not suit a project that requires uninterrupted continuous coverage.

Requesting Dimensional Reports After Production

Measurement points, sampling, and reporting requirements should be agreed before manufacturing.

Confusing Thickness with Electrical Class

A thicker mat is not automatically a higher-class mat. Electrical class must be supported by the applicable standard and test evidence.

How We Review a Bulk Matting Inquiry

When we receive a bulk insulating mat inquiry, we review the dimensions in a fixed order.

We Confirm the Standard and Electrical Class

We start with the required electrical performance rather than thickness alone.

We Confirm the Nominal Thickness

We review the target thickness, surface pattern, and selected class.

We Define the Thickness Reporting Method

We confirm the measurement reference, supplier range, sampling, and reporting format.

We Confirm Nominal and Usable Width

We identify whether warning borders, trimming, or other features are included.

We Define the Roll-Length Requirement

We confirm whether the stated length is nominal or a guaranteed minimum.

We Confirm Whether Joints Are Permitted

Continuous-roll requirements are agreed before production.

We Review Quantity and Area Calculation

We confirm whether the commercial quantity is based on rolls, nominal area, or measured area.

We Agree on Sampling and Records

The buyer and supplier confirm how many rolls will be measured and how the results will be recorded.

We Confirm Roll Marking and Packing

Roll IDs, batch details, labels, core size, wrapping, and pallet protection are reviewed.

We Declare Dimensional Deviations

Any difference from the RFQ should be approved before production.

For substations and other power projects, dimensional requirements should also match the application layout. See our substation electrical safety application guide 전력 엔지니어링 안전 솔루션.

FAQ

Does IEC 61111 give a general thickness tolerance?

No. IEC 61111 does not provide one universal ±X% thickness tolerance. It defines maximum thickness by class, while minimum thickness depends on the product’s ability to pass the required tests. A manufacturer or buyer may define an additional production tolerance.

What is the IEC 61111 tolerance for length and width?

The manufacturer-declared length and width should remain within ±2% of the stated dimensions. A project may require stricter contractual limits.

Can a nominal 10 m roll be shorter than 10 m?

Yes, when the agreed purchasing basis permits negative length tolerance. If the project requires at least 10 m of usable material, specify a minimum guaranteed continuous length.

How should corrugated or diamond mat thickness be measured?

IEC 61111 states that measurements should be made over the corrugations or diamonds. The report should identify the measurement reference clearly.

Does a thicker mat have a higher electrical rating?

Not automatically. Electrical class depends on the applicable standard and verified performance, not thickness alone.

Should a yellow warning edge be included in the total width?

The RFQ should state this clearly. Define the full finished width, warning-border width, and central usable width separately.

Should buyers accept spliced rolls?

Only when joins are permitted by the purchase specification and suitable for the application. Projects requiring continuous coverage should prohibit unapproved joins.

How many rolls should be measured?

The sampling plan depends on order size, project risk, contract requirements, and inspection method. The number or percentage should be agreed before production.

What documents should accompany the shipment?

Depending on the order, buyers may request a datasheet, dimensional inspection report, test report, Certificate of Conformity, roll list, batch record, marking sample, and packing list.

실용적인 구매자 요약

Do not approve a bulk electrical insulating mat order from nominal dimensions alone.

A specification such as 5 mm × 1 m × 10 m should be supported by clear answers to the following questions:

  • 어떤 기준이 적용되나요?
  • Which electrical class is required?
  • What is the nominal thickness?
  • What production thickness range is declared?
  • Where will thickness be measured?
  • What is the nominal width?
  • What is the minimum usable width?
  • Are warning borders included?
  • Is the roll length nominal or guaranteed?
  • Is negative length tolerance accepted?
  • Must every roll be continuous?
  • Are joins permitted?
  • Is quantity based on nominal or measured area?
  • How many rolls will be inspected?
  • What documents will identify each roll?

The most important technical distinction is:

IEC 61111 applies a dimensional tolerance to declared length and width, while thickness follows a different standard and product-control logic.

A clear purchasing process should connect:

Standard and class → nominal dimensions → agreed tolerances → measurement method → production records → roll marking → incoming inspection

Confirm these requirements before production. This reduces dimensional disputes, coverage shortages, unclear invoicing, and rejected deliveries.

현지 규정 및 현장 안전 절차를 준수하십시오.

정보를 입력하세요